S7

The S7 PLC component is an S7comm (Siemens S7 communication) client for Siemens programmable logic controllers (PLCs). It connects to one PLC and polls the addresses you list in its point map, publishing each one as a Profinity tag. It supports S7-300, S7-400, S7-1200, and S7-1500 controllers. The S7 plugin requires the Industrial Protocols licensed component group, and Install an industrial protocol plugin explains how to obtain, install, and licence it.

flowchart LR
    PLC["Siemens PLC"]
    subgraph Profinity
        Component["S7 PLC"] --> Tags
    end
    PLC --> Component
The S7 PLC component in Profinity polls the addresses in its point map from one Siemens PLC and publishes each as a Profinity tag

Add an S7 PLC to your Profile from the Industrial Protocols group in the component catalogue, as described in How to add a component to your profile. Add one component for each PLC you want to read. You can change the settings in the Communications settings section later from the component's Change Settings menu action.

You specify the memory area and byte offset of each value. Symbolic tag names are not supported. For symbolic access to an S7-1200 or S7-1500, use the OPC UA Client against the PLC's Open Platform Communications Unified Architecture (OPC UA) server.

Before you add the component, prepare the PLC:

  • Enable Put/Get access on S7-1200 and S7-1500 PLCs, which do not answer without it.
  • Do not use optimised block access on data blocks, because optimised blocks cannot be read by absolute address.

Whoever maintains the PLC program changes both in the PLC's project, in the Siemens engineering software (TIA Portal).

Communications settings

Setting Description
Name The name of the component. Must be unique within the profile.
Host The IP address of the PLC. Required. The default is 127.0.0.1.
Port The Transmission Control Protocol (TCP) port. Between 1 and 65535. The default is 102.
Rack The rack number of the PLC. Between 0 and 7. The default is 0.
Slot The slot number of the CPU (central processing unit). Between 0 and 31. The default is 1.
CPU type The PLC family: S7-300, S7-400, S7-1200 (the default) or S7-1500.
Poll interval (ms) How often the point map is read, in milliseconds. Between 50 and 600000. The default is 1000.
Request timeout (ms) How long Profinity waits for the PLC to answer a request, in milliseconds. Between 50 and 60000. The default is 1000.
Reconnect delay (ms) How long Profinity waits between connection attempts, in milliseconds. Between 0 and 600000. The default is 2000.
Auto Connect Connects to the PLC automatically when the profile is loaded. Off by default, as described in Connections and reconnecting.

Profinity keeps trying to connect when the PLC is down at start and after a connection is lost, as described in Connections and reconnecting.

The usual rack and slot is 0 and 1 for S7-1200 and S7-1500 controllers, and 0 and 2 for most S7-300 controllers. Confirm the values in the PLC's hardware configuration.

Point map

The point map lists the PLC addresses to read. Each row becomes one tag.

Column Description
Name The name of the tag, published under the component's Points tags. Use a unique name for each row.
Area The memory area: DataBlock (the default), Memory (M), Input (I) or Output (Q).
DB number The data block number. Used only when the area is DataBlock, and ignored otherwise. The default is 1.
Offset The byte offset within the selected area.
Data type How the value is read: Boolean, Word (the default), SignedWord, Dword, SignedDword or Real.
Writable Allows Profinity to write the PLC value from the tag. Off by default.
Unit An optional unit label for the tag.

The data types map to the width of the value in the PLC, and to the type of the Profinity tag.

Data type Size Profinity tag
Boolean 1 bit (bit 0 of the byte) Boolean
Word / SignedWord 2 bytes (unsigned / signed) Integer
Dword / SignedDword 4 bytes (unsigned / signed) Integer
Real 4 bytes (floating point) Number

A Boolean point always reads bit 0 of the byte at its offset, because the point map has no bit number. The PLC program must therefore place the value you need in bit 0 of a byte. At offset 10, the address each point reads is:

Area and data type Address read
DataBlock 1, Boolean DB1.DBX10.0
DataBlock 1, Word DB1.DBW10
DataBlock 1, Dword or Real DB1.DBD10
Memory, Word MW10
Input, Word IW10
Output, Word QW10

Siemens tools set to German show the input and output areas as E and A rather than I and Q.

Writing to a PLC

A write can change the controlled process, so turn Writable on only for values that must be set from Profinity.

Dashboard

The component dashboard shows the connection STATUS and whether the PLC is CONNECTED. It also shows the number of values read (RECEIVED) and values written (SENT). Use the Connect / Disconnect menu action to start or stop polling manually. Viewing the dashboard requires the Security administration permission, described under Roles and permissions.

Polled values behave like any other tag, so they can be shown on a dashboard, logged, watched by a rule, or read by a script.

If a point shows bad quality

If a point cannot be read, its tag is marked as bad quality. Check the usual causes in this table before reading the Log for the reason.

Cause Fix
Put/Get access is disabled on the PLC. Enable Put/Get access in the PLC's project.
A data block uses optimised block access. Turn off optimised block access for the data block in the PLC's project.
Rack or Slot is wrong. Set the values from the PLC's hardware configuration.
The PLC does not have the DB number or Offset. Correct the point map row to an address that exists in the PLC.

Refer to Connections and reconnecting for how the Log records failed reads and recovery.