Connections and reconnecting

Every component that holds a connection behaves the same way when it starts, when the other end is missing, and when a connection is lost. This covers these components:

  • The Message Queuing Telemetry Transport (MQTT) Publisher and Subscriber.
  • The Tag Relay sender and receiver.
  • The SQL and InfluxDB historians and loggers, and the Prometheus logger.
  • The chargers.
  • The CAN bus adapters.
  • The Open Platform Communications Unified Architecture (OPC UA) server and client.
  • The Modbus, BACnet, S7, and EtherNet/IP components.

A CAN bus adapter adds a warning when the bus is quiet, as described under Status.

Turning connections on and off

Every one of these components except the Elcon charger has the same Auto Connect setting. The Elcon charger has no Auto Connect setting, because it communicates over CAN and has no connection step. Auto Connect decides only whether the connection is made when the profile loads. After that the component is a switch that you turn on with Connect (or Start) and off with Disconnect (or Stop).

  • With Auto Connect on, the component connects when the profile loads.
  • With Auto Connect off, the component stays Off and makes no connection attempt until you switch it on.
  • Switched on, the component keeps trying until it is connected. Switched off, it stops trying and stays off, and loading or changing the profile does not switch it back on.

The default depends on the kind of component:

Component Auto Connect default
CAN bus adapters, loggers, historians, the MQTT Subscriber, and the Tag Relay sender and receiver On
TDK and Siglent power supplies, and the Modbus, BACnet, S7, EtherNet/IP, and OPC UA components Off

For a component that defaults to off, turn Auto Connect on in its settings if it should connect whenever the profile loads.

Starting when the other end is not there

A component starts even when what it connects to is not available. It does not stop at start with an error. It shows Error, writes the reason to the Logs once, and keeps trying. The TDK and Siglent power supplies have an Auto Reconnect setting, and with it off they make one attempt and report a failure. When the broker, device, server, or database appears, the component connects by itself and the status changes to On.

This includes a login that is rejected. Profinity keeps trying and shows the reason, so fixing the credentials in the settings needs no restart.

Recovering from a lost connection

If a connection is lost while the component is running, it goes to Error and tries again in the same way. The log records the first connection failure of an outage at error level and the later attempts at debug level, so a long outage does not fill the log. When the connection returns, the log records that it reconnected.

When reads, writes, or sends keep failing

A component can be connected and still fail to read a value, write a point or send a message. Profinity reports that once for each outage. The first failure is written to the Logs as a warning that names what failed and why. Later failures during the same outage are logged at debug level only, and the first success afterwards is logged at information level as the component working again. The first success is the first poll in which every point reads correctly. A long outage does not fill the log, and a new outage warns again. This also applies to a poll that fails as a whole.

The Modbus, BACnet, S7, EtherNet/IP and OPC UA client components log failed point reads in this way.

Retry timing

Profinity retries every 5 seconds unless the component has its own setting.

Component Retry interval
Chargers Reconnect Interval setting (default 5000 ms), when Auto Reconnect is on
Modbus, BACnet, S7, EtherNet/IP, OPC UA client Reconnect delay (ms) setting
Tag Relay sender 1 second
All others 5 seconds

Stopping

Stopping a component, or removing it, stops the retries and closes the connection. A stopped component never reconnects by itself.

Status

Status Meaning
Off The component is stopped, or has just been switched on and is making its first connection attempt.
On The connection is up.
Error The component is running but cannot reach what it connects to. Check the Logs for the reason.

A logger or historian shows On as soon as it is started, and changes to Error if it cannot reach its server. A CAN bus adapter connects and retries in the same way, and adds a warning for a quiet bus. While it is stopped, or still making its first connection attempt, it shows Off. When a connection it was asked to make fails or is lost, it shows Error and keeps retrying. Once connected, it shows On while CAN frames are arriving. A Tritium bridge heartbeat is a CAN frame, so a bridge that is only sending heartbeats stays On. A connected adapter that has never seen a frame, or whose last frame is more than 5 seconds old, shows a warning (amber). Exactly 5 seconds since the last frame stays On. Choosing Disconnect shows Off, and the adapter does not retry until you connect it again. Check the Logs for the reason an adapter is not connecting.

To see how the protocol components use these settings, refer to Industrial protocols.