S7

The S7 PLC component is an S7comm (Siemens S7 communication) client for Siemens programmable logic controllers (PLCs). It connects to one PLC and polls the addresses you list in its point map, publishing each one as a Profinity tag. It supports S7-300, S7-400, S7-1200, and S7-1500 controllers. The S7 plugin requires the Industrial Protocols licensed component group, and Install an industrial protocol plugin explains how to obtain, install, and licence it.

flowchart LR
    PLC["Siemens PLC"]
    subgraph Profinity
        Component["S7 PLC"] --> Tags
    end
    PLC --> Component
The S7 PLC component in Profinity polls the addresses in its point map from one Siemens PLC and publishes each as a Profinity tag

Add an S7 PLC to your Profile from the Industrial Protocols group in the component catalogue, as described in How to add a component to your profile. Add one component for each PLC you want to read. You can change the settings in the Communications settings section later from the component's Change Settings menu action.

You specify the memory area and byte offset of each value. Tags are addressed by memory area and byte offset, not by symbolic tag name. For symbolic access to an S7-1200 or S7-1500, use the OPC UA Client against the PLC's Open Platform Communications Unified Architecture (OPC UA) server.

Before you add the component, prepare the PLC:

  • Enable Put/Get access on S7-1200 and S7-1500 PLCs, which answer only when it is enabled.
  • Use standard block access on data blocks, because optimised blocks cannot be read by absolute address.

Whoever maintains the PLC program changes both in the PLC's project, in the Siemens engineering software (TIA Portal).

Quick start

You need the Industrial Protocols licensed component group, a PLC that the Profinity server can reach on the network, Put/Get access enabled on an S7-1200 or S7-1500 PLC, and standard block access on each data block the points read.

  1. Add an S7 PLC from the Industrial Protocols group in the component catalogue.
  2. Set Host to the IP address of the PLC. The default, 127.0.0.1, is the loopback address of the local machine.
  3. If the PLC is not an S7-1200, set CPU type to match it. The default is S7-1200.
  4. Add one row to the Point map with a Name and an Offset, and set Data type to match the value. Area and DB number keep their defaults, DataBlock and 1.
  5. Select ADD COMPONENT at the bottom of the dialog.
  6. If Auto connect is off, which is its default, switch the component on with the Connect / Disconnect menu action.
  7. On the component dashboard, check that STATUS shows Connected and CONNECTED is true. The tag for your row, under the component's Points tags, shows Good quality and its value.

Communications settings

Setting Type Default Description
Name Text S7 PLC The name of the component. Must be unique within the profile.
Host Text 127.0.0.1 The IP address of the PLC. Required.
Port Whole number 102 The Transmission Control Protocol (TCP) port. Between 1 and 65535.
Rack Whole number 0 The rack number of the PLC. Between 0 and 7.
Slot Whole number 1 The slot number of the CPU (central processing unit). Between 0 and 31.
CPU type Choice S7-1200 The PLC family. The settings dialog lists S7-300, S7-400, S7-1200 and S7-1500, and the profile file holds S7300, S7400, S71200 or S71500, without the hyphen.
Poll interval (ms) Time 1000 How often the point map is read, in milliseconds. Between 50 and 600000.
Request timeout (ms) Time 1000 How long Profinity waits for the PLC to answer a request, in milliseconds. Between 50 and 60000.
Reconnect delay (ms) Time 2000 How long Profinity waits between connection attempts, in milliseconds. Between 0 and 600000.
Auto connect On or off Off Connects to the PLC automatically when the profile is loaded, as described in Connections and reconnecting.

With Auto connect on, profinity keeps trying to connect when the PLC is down at start and after a connection is lost, as described in Connections and reconnecting. With Auto connect off, it connects only after you switch the component on.

Take the Rack and Slot values from the PLC's hardware configuration.

Point map

The point map lists the PLC addresses to read. Each row becomes one tag. This component has no Browse button, because an S7 PLC does not publish the variables inside a data block. Folders are described in Industrial protocol components.

Column Type Default Description
Name Text - The name of the tag under the component's Points tags. It must be unique in its folder. The same name can be used in another folder.
Area Choice DataBlock The memory area: DataBlock, Memory (M), Input (I) or Output (Q).
DB number Whole number 1 The data block number. Used only when the area is DataBlock, and ignored otherwise.
Offset Whole number 0 The byte offset within the selected area.
Data type Choice Word How the value is read: Boolean, Word, SignedWord, Dword, SignedDword or Real.
Writable On or off Off Allows Profinity to write the PLC value from the tag.
Unit Text - An optional unit label for the tag.

The data types map to the width of the value in the PLC, and to the type of the Profinity tag.

Data type Size Profinity tag
Boolean 1 bit (bit 0 of the byte) Boolean
Word / SignedWord 2 bytes (unsigned / signed) Integer
Dword / SignedDword 4 bytes (unsigned / signed) Integer
Real 4 bytes (floating point) Number

A Boolean point always reads bit 0 of the byte at its offset, because the point map has no bit number. The PLC program must therefore place the value you need in bit 0 of a byte. At offset 10, the address each point reads is, for example:

Area and data type Address read
DataBlock 1, Boolean DB1.DBX10.0
DataBlock 1, Word DB1.DBW10
DataBlock 1, Dword or Real DB1.DBD10
Memory, Word MW10
Input, Word IW10
Output, Word QW10

Writing to a PLC

A write can change the controlled process, so turn Writable on only for values that must be set from Profinity.

Example

Add this example under components: in the profile.yaml file of the profile, and replace PLC_IP_ADDRESS with the IP address of your PLC. The port, rack, slot, CPU type and timings are the defaults from the settings table, so change them only to suit your PLC. The example sets Auto connect on, so the component connects when the profile loads.

- component:
    type: S7Plc
    id: S7Plc1
    name: Line 1 PLC
    tagTreeParentPath: /
    host: PLC_IP_ADDRESS
    port: 102
    rack: 0
    slot: 1
    cpuType: S71200
    pollIntervalMilliseconds: 1000
    requestTimeoutMilliseconds: 1000
    reconnectDelayMilliseconds: 2000
    autoConnect: true
    points:
    - name: Setpoint
      area: DataBlock
      dbNumber: 1
      offset: 10
      dataType: Real
      writable: false

This component reads the four bytes at DB1.DBD10 once a second and publishes them as the Number tag Setpoint under the component's Points tags.

Dashboard

The component dashboard shows the connection STATUS and whether the PLC is CONNECTED. It also shows the number of values read (RECEIVED) and values written (SENT). Use the Connect / Disconnect menu action to start or stop polling manually. Viewing the dashboard requires the Security administration permission, described under Roles and permissions.

Polled values behave like any other tag, so they can be shown on a dashboard, logged, watched by a rule, or read by a script.

If a point shows bad quality

If a point cannot be read, its tag is marked as bad quality. Check the usual causes in this table before reading the Log for the reason.

What you see Cause What to do
A point shows bad quality. Put/Get access is disabled on the PLC. Enable Put/Get access in the PLC's project.
A point shows bad quality. A data block uses optimised block access. Turn off optimised block access for the data block in the PLC's project.
A point shows bad quality. Rack or Slot is wrong. Set the values from the PLC's hardware configuration.
A point shows bad quality. The PLC does not have the DB number or Offset. Correct the point map row to an address that exists in the PLC.

Refer to Connections and reconnecting for how the Log records failed reads and recovery.