OPC UA Server

The OPC UA Server lets Open Platform Communications Unified Architecture (OPC UA) clients, such as a supervisory control and data acquisition (SCADA) or historian system, read the live values in a Profinity profile. It publishes the profile's tags as a read-only address space, which is the tree of nodes that an OPC UA client browses. It sits in the Industrial Protocols group, and the same plugin provides the OPC UA Client, which can run on its own or beside the server.

flowchart LR
    Tags --> Server["OPC UA Server"] --> Consumer["Third-party OPC UA client"]
The OPC UA Server publishes the Profinity tag tree to third-party OPC UA clients as a read-only address space

Quick start

You need:

  • An edition with the Industrial Protocols licensed component group, and the OPC UA plugin installed, as described in Install an industrial protocol plugin.
  • The Security administration permission to view the component dashboard in step 5.

  • Select ADD COMPONENT, then select OPC UA Server in the Industrial Protocols group.

  • Keep Bind URL as opc.tcp://127.0.0.1:4840/Profinity, which accepts clients on this computer only. To accept other computers, change it as described in Listening address.
  • Select ADD COMPONENT.
  • Select Start / Stop from the component's menu. Auto connect is off by default.
  • On the component dashboard, check that STATUS shows Listening and LISTENING is true.

To check from a client, connect it to the Bind URL and browse Objects > Profinity.

Settings

Setting Type Default Description
Name Text OPC UA Server The name of the component. Must be unique within the profile.
Bind URL Text opc.tcp://127.0.0.1:4840/Profinity The address the server listens on, which is also the address clients connect to. Required, and must start with opc.tcp://.
Auto connect On or off Off Starts the server when the profile loads, as described in Connections and reconnecting.
Trust all client certificates On or off Off When on, the server accepts any client certificate. When off, it refuses a certificate that is not in its trusted folder and stores it in rejected. Turn it on only on a trusted network.

To change the settings later, select Change Settings from the component's menu. For where the server keeps its certificates, refer to OPC UA certificates.

Tags

The server reads every tag in the profile that holds a single readable value, and publishes no tags of its own. In the address space, the tags sit under Objects > Profinity, the folder with the NodeId ns=2;s=Profinity. Each tag is a node whose NodeId is ns=2;s= followed by the tag's tag tree path, so the tag Inverter/DBC/Status/Speed is ns=2;s=Inverter/DBC/Status/Speed.

The address space is read-only, so clients can view values and cannot change them. The server builds it when it starts, from the tags that are readable then, so a tag added to the profile later appears after the server restarts. A tag with no sample, or with a null value, reads as BadNoData.

Example

This example accepts clients on the network at one address of the Profinity computer. Add it under components: in the profile.yaml file of the profile.

- component:
    type: OpcUaServer
    id: OpcUaServer1
    name: Plant OPC UA Server
    tagTreeParentPath: /
    bindUrl: opc.tcp://SERVER_ADDRESS:4840/Profinity
    autoConnect: true
    trustAllClientCertificates: false

Replace SERVER_ADDRESS with an IP address of the Profinity computer that your OPC UA clients can reach.

Listening address

With the default Bind URL, the server listens on the loopback address 127.0.0.1, so only clients on the Profinity computer can connect. A Bind URL with the host 0.0.0.0 or localhost also listens on 127.0.0.1 only.

To accept clients on other computers, replace the host in the Bind URL, for example opc.tcp://192.168.1.20:4840/Profinity:

  • An IP address listens on that address only.
  • A host name other than localhost listens on every address of the computer.

The server accepts anonymous clients without message security

Messages are not signed or encrypted, and any client can connect. Accept clients from other computers only on a network you trust.

The server certificate names the host in the Bind URL. When the server starts with a host that the certificate does not name, such as after you change the Bind URL, Profinity deletes the old certificate and its private key and creates new ones. To keep the old certificate, copy the own folder from the opcua_pki folder first, as described in OPC UA certificates. Each client then refuses the new certificate until you trust it on the client.

Dashboard

The dashboard shows the server STATUS, whether it is LISTENING, and the number of client requests RECEIVED and responses SENT since it last started listening. Viewing it needs the Security administration permission, as described in Roles and permissions.

Troubleshooting

For the reason behind a failure, read the Logs page under ADMIN.

What you see Cause What to do
A client on another computer cannot connect The Bind URL listens on 127.0.0.1 only. Set the host in the Bind URL to an address those clients can reach, as described in Listening address.
A tag added to the profile is missing from the address space The server builds the address space when it starts. Select Start / Stop from the component's menu to stop the server, then select it again to start it.
A tag reads as BadNoData The tag has no sample, or its value is null. Check in TAG EXPLORER that the tag has a value.
A client cannot write a value The address space is read-only. Change the value at its source in Profinity.
A client refuses to connect after the Bind URL changes Profinity created a new server certificate for the new host. Trust the new certificate on the client.
The server refuses a client certificate The certificate is not in the server's trusted folder, so the server stored it in rejected. Check the certificate, then move it from rejected to trusted, as described in OPC UA certificates.