OPC UA Client

The OPC UA Client connects to a remote Open Platform Communications Unified Architecture (OPC UA) server and polls the nodes you list into Profinity tags. Use it to bring values from a programmable logic controller (PLC), a supervisory control and data acquisition (SCADA) system or another OPC UA server into Profinity. Add one client for each server you want to read. The OPC UA plugin also provides the OPC UA Server, and the two components can be used on their own or together.

For a Siemens S7-1200 or S7-1500, the OPC UA Client against the PLC's built-in OPC UA server lets you read symbolic tags by name, which the S7 component cannot do.

flowchart LR
    Source["Remote OPC UA server"] --> Client["OPC UA Client"] --> Tags
The OPC UA Client polls nodes from a remote OPC UA server into Profinity tags

Licence required

The OPC UA plugin requires the Industrial Protocols licensed component group, and Install an industrial protocol plugin explains how to obtain, install, and licence it.

Add the client to your Profile from the Industrial Protocols group in the component catalogue, as described in How to add a component to your profile. You can change the settings in the Settings section later from the component's Change Settings menu action.

Viewing the dashboard requires the Security administration permission, described under Roles and permissions.

Quick start

  1. Set Endpoint URL to the address of the server, starting with opc.tcp://.
  2. Check that Name is unique within the profile. The default is OPC UA Client.
  3. In the Points tab, select New point, then enter a Name and a NodeId.
  4. Select Save.
  5. If Auto connect is off, which is its default, switch the component on with the Connect / Disconnect menu action.
  6. On the component dashboard, check that STATUS shows Connected and CONNECTED is true. The tags under the component's Points tags show Good quality and a changing value.

Settings

Setting Type Default Description
Name Text OPC UA Client The name of the component. Must be unique within the profile.
Endpoint URL Text opc.tcp://127.0.0.1:4840 The address of the server. Required, and must start with opc.tcp://.
Use security On or off Off When off, the client connects without message security. Turn it on to connect to an endpoint that uses security (message signing or encryption). When the server offers no such endpoint, the connection fails with the message "No OPC UA endpoint was selected for" and the address, and Profinity does not fall back to an unsecured connection.
Username Text Empty An optional user name. Leave it empty to connect anonymously.
Password Secret Empty The password for the user name. It is stored encrypted.
Trust all server certificates On or off Off Skips validation of the server's certificate. Turn it on only when connecting to a trusted endpoint that uses a self-signed certificate.
Poll interval (ms) Whole number (ms) 1000 How often the node map is read, in milliseconds. Between 50 and 600000.
Request timeout (ms) Whole number (ms) 5000 How long Profinity waits for the server to answer a request, in milliseconds. Between 50 and 60000.
Reconnect delay (ms) Whole number (ms) 2000 How long Profinity waits between connection attempts, in milliseconds. Between 0 and 600000.
Auto connect On or off Off Connects to the server automatically when the profile is loaded, as described in Connections and reconnecting.

With Auto connect on, Profinity keeps trying to connect when the server is down at start and after a connection is lost, as described in Connections and reconnecting. With Auto connect off, it connects only after you switch the component on.

Trusting certificates

Trust all server certificates removes the check that proves you are talking to the server you intended. Use it only on a trusted network, and where you can, place the server's certificate in the trusted folder instead, as described in OPC UA certificates.

Point map

The point map lists the OPC UA nodes to read. Each row becomes one tag.

Folders and Browse are described in Industrial protocol components. Browse the server once the client is connected:

  1. Select Save.
  2. On the component dashboard, check that STATUS shows Connected and CONNECTED is true.
  3. Select Browse. It lists the saved server one folder at a time, using the endpoint last saved. If the client is not connected, Browse shows "OPC UA client is not connected."
Column Type Default Description
Name Text Empty The name of the tag under the component's Points tags. It must be unique in its folder. The same name can be used in another folder.
NodeId Text Empty The identifier of the node on the server, for example ns=2;s=Temp.
Writable On or off Off Allows Profinity to write the node from the tag. Nodes stay read-only unless you turn this on.
Unit Text Empty An optional unit label for the tag.

Example

This example is for illustration only. Add this list item under the existing components: key in the profile.yaml file of the profile, and replace OPC_SERVER_HOST with the address of your OPC UA server.

- component:
    name: Plant OPC UA Client
    type: OpcUaClient
    endpointUrl: opc.tcp://OPC_SERVER_HOST:4840
    useSecurity: false
    pollIntervalMilliseconds: 1000
    requestTimeoutMilliseconds: 5000
    reconnectDelayMilliseconds: 2000
    autoConnect: true
    points:
      - name: Temp
        nodeId: ns=2;s=Temp
        writable: false

This client reads the node ns=2;s=Temp once a second and publishes it as the tag Temp under the component's Points tags.

Dashboard

The component has a dashboard showing its STATUS and whether it is CONNECTED to the server. It also shows the number of values read (RECEIVED) and values written (SENT). The client has a Connect / Disconnect menu action.

Values polled by the client behave like any other tag, so they can be shown on a dashboard, logged, watched by a rule, or read by a script.

If a point shows bad quality

Each point's tag is created as soon as its row exists and shows Unavailable quality until the first poll reads it. After that a successful read gives Good quality, and a node that cannot be read is marked as Bad quality. Check the usual causes in this table before reading the Log for the reason.

What you see Cause What to do
A point shows Bad quality The server does not have the NodeId. Correct the point map row to a node that exists on the server.
STATUS does not show Connected The Endpoint URL does not start with opc.tcp://, or cannot be reached. Enter the server's address starting with opc.tcp://, and check that Profinity can reach it.
STATUS does not show Connected The server certificate is in the rejected folder. Move the certificate into trusted once you have confirmed it, as described in OPC UA certificates.

Refer to Connections and reconnecting for how the Log records failed reads and recovery.