Modbus

The Modbus Device component is a Modbus master. It connects to one Modbus slave over Transmission Control Protocol (TCP) or over a serial line using Remote Terminal Unit (RTU) framing.

It polls the coils and registers you list in its point map and publishes each one as a Profinity tag. Modbus is used for industrial devices and distributed input/output (I/O). Profinity acts as a Modbus master only, not as a Modbus slave or server.

flowchart LR
    Slave["Modbus slave"]
    subgraph Profinity
        Component["Modbus Device"] --> Tags
    end
    Slave --> Component
The Modbus Device component in Profinity polls the coils and registers in its point map from one Modbus slave and publishes each as a Profinity tag

Licence required

The Modbus plugin requires the Industrial Protocols licensed component group, and Install an industrial protocol plugin explains how to obtain, install, and licence it.

Add a Modbus Device to your Profile from the Industrial Protocols group in the component catalogue, as described in How to add a component to your profile. Add one component for each slave you want to read. You can change the settings in the Communications settings section later from the component's Change Settings menu action.

Quick start

You need a Modbus TCP slave that this computer can reach over the network, and its IP address. Viewing the dashboard needs you to be signed in and allowed to see the component.

  1. Select ADD COMPONENT, then select Modbus Device in the Industrial Protocols group.
  2. Leave Connection mode as TCP, and set Host to the IP address of the slave.
  3. In the Point map, add one row with a Name and the Address of the register. Leave Table as HoldingRegister and Data type as Word.
  4. Select ADD COMPONENT at the bottom of the dialog.
  5. If Auto connect is off, which is its default, select Connect / Disconnect from the component's menu to start polling.
  6. On the component dashboard, check that STATUS shows Connected and CONNECTED is true.

Communications settings

Which settings apply depends on the Connection mode.

Setting Type Default Applies to Description
Name Text Modbus Device Both The name of the component. Must be unique within the profile.
Connection mode Choice Tcp Both Tcp or Rtu, shown as TCP or RTU in the UI.
Host Text 127.0.0.1 TCP The IP address of the slave. Required.
Port Whole number 502 TCP The TCP port. Between 1 and 65535.
Serial port Choice Empty RTU The serial port the slave is connected to. Required for RTU.
Baud rate Whole number 9600 RTU The serial baud rate.
Parity Choice None RTU The serial parity.
Data bits Whole number 8 RTU 7 or 8.
Stop bits Choice One RTU The number of stop bits.
Unit ID Whole number 1 Both The Modbus unit (slave) address. Between 0 and 255.
Poll interval (ms) Time 1000 Both How often the point map is read, in milliseconds. Between 50 and 600000.
Request timeout (ms) Time 1000 Both How long Profinity waits for the slave to answer a request, in milliseconds. Between 50 and 60000.
Reconnect delay (ms) Time 2000 Both How long Profinity waits between connection attempts, in milliseconds. Between 0 and 600000.
Auto connect On or off Off Both Connects automatically when the profile is loaded. Off by default, as described in Connections and reconnecting.

With Auto connect on, profinity keeps trying to connect when the device is down at start and after a connection is lost, as described in Connections and reconnecting. With Auto connect off, it connects only after you switch the component on.

Match the serial settings to those configured on the slave. If they differ, the slave does not answer.

Point map

The point map lists the coils and registers to read. Each row becomes one tag. This component has no Browse button, because a Modbus device does not publish a register list. Folders are described in Industrial protocol components.

Column Type Default Description
Name Text None The name of the tag under the component's Points tags. It must be unique in its folder. The same name can be used in another folder.
Table Choice HoldingRegister The Modbus table to read: Coil, DiscreteInput, HoldingRegister or InputRegister.
Address Whole number 0 The zero-based protocol address. Register 40001 in a one-based manufacturer's manual is address 0 of the holding registers.
Data type Choice Word How the value is decoded: Boolean, Word, SignedWord, Dword, SignedDword or Real.
Scale Decimal number 1 A factor that reads are multiplied by. Writes are divided by the same factor.
Writable On or off Off Allows Profinity to write the value from the tag.
Unit Text None An optional unit label for the tag.

Registers are read as big-endian values. Word and SignedWord use one register. Dword, SignedDword and Real use two consecutive registers starting at the address, with the first register holding the high word.

The component has no word-swap option, so a device that sends the low word first returns wrong 32-bit values. Real is a 32-bit floating point value.

Use Scale for devices that report fixed-point values. For example, a temperature held as tenths of a degree uses a scale of 0.1.

A Coil or DiscreteInput row always reads a single on/off bit, and its Data type is not used. A Boolean row on a HoldingRegister or InputRegister table reads one register and is true when the register is not zero.

Only the HoldingRegister and Coil tables can be written. DiscreteInput and InputRegister points are always read-only, even if Writable is on.

Writing to a device

Leave Writable off for any point that Profinity should only monitor, because a write changes the device.

Example

This example is for illustration. It reads a temperature held as tenths of a degree from a holding register, and switches a pump through a coil, on a Modbus TCP slave. Add it under components: in the profile.yaml file of the profile.

- component:
    type: ModbusDevice
    id: ModbusDevice1
    name: Pump Controller
    tagTreeParentPath: /
    connectionMode: Tcp
    host: SLAVE_IP_ADDRESS
    port: 502
    unitId: 1
    pollIntervalMilliseconds: 1000
    requestTimeoutMilliseconds: 1000
    reconnectDelayMilliseconds: 2000
    autoConnect: true
    points:
    - name: Temperature
      table: HoldingRegister
      address: 0
      dataType: Word
      scale: 0.1
      writable: false
      unit: °C
    - name: PumpRunning
      table: Coil
      address: 0
      writable: true

Replace SLAVE_IP_ADDRESS with the IP address of your Modbus slave. Profinity fills in a missing or duplicate id, and a missing tagTreeParentPath (set to /), when it loads the profile, so you can leave them out. Set name, the connection settings and points. type names the component kind, so keep it as shown. Each value is a setting from the Communications settings or a column from the Point map.

Dashboard

The component dashboard shows the connection STATUS (Connected, Not connected; retrying, or Disconnected) and whether the device is CONNECTED. Disconnected means polling has not started. Not connected; retrying means polling has started and the device is not connected yet. If the status is Disconnected, check the Log. It also shows the number of values read (RECEIVED) and values written (SENT). Use the Connect / Disconnect menu action to start or stop polling manually. Viewing the dashboard needs you to be signed in and allowed to see this component, as described under Component and collection security.

Polled values behave like any other tag, so they can be shown on a dashboard, logged, watched by a rule, or read by a script.

If a point shows bad quality

If a point cannot be read, its tag is marked as bad quality. Check the usual causes in this table before reading the Log for the reason.

What you see Cause What to do
The point is marked as bad quality. The Address is one higher or lower than the device manual states. Use the zero-based protocol address. Register 40001 in a one-based manual is address 0 of the holding registers.
The point is marked as bad quality. The Unit ID differs from the slave. Set Unit ID to the slave's unit address.
The point is marked as bad quality. The serial settings differ from the slave. Match Baud rate, Parity, Data bits and Stop bits to those configured on the slave.
The point is marked as bad quality. The Data type does not match the register. Choose the data type that matches the register.

Refer to Connections and reconnecting for how the Log records failed reads and recovery.